321
)

BIOROCK Independent Test Results

BIOROCK Independent Test Results

Posted on 30 Jan 2013 by Biorock

BIOROCK Independent Test Results

The effluent from a sewage treatment unit is measured in terms of the Biological Oxygen Demand (BOD), the Suspended Solids (SS), and the Ammonia (NH3). It is expressed in the form BOD:SS:NH3 and is measured in mg/L

Effluent Quality of BIOROCK sewage treatment units

The Royal Commission Standard for effluent quality from sewage treatment units in the UK is 20:30:20 (BOD:SS:NH3). To understand these figures, septic tank effluent is around 120 :180 :80 and distilled water is 0:0:0, so obviously, the lower the figures the better the quality.

Performance of BIOROCK sewage treatment units.

The BIOROCK sewage treatment unit has been tested to EN12566-3 2005 and the EN12566-7 2006 standard in the EU testing facility PIA in Aachen, Germany. Only sewage plants that have this standard are able to apply for the Discharge or Exemption Permit from the Environment Agency. The table below summarizes the results from the extensive 38 weeks of independent EN testing on the BIOROCK 6 sewage treatment units. Essentially the independent testing showed that the BIOROCK sewage treatment unit produces a very high-quality secondary effluent, far better than almost all aquatic systems.

When tested at The EN Test Centre, the BIOROCK consistently produced an effluent quality (in mg/L) of (BOD:SS:NH3) > 4:3:3. Given normal use, BIOROCK sewage treatment units exceeded normal UK standards of "20BOD:30S.S." by five times.

EN 12566-3 2005

Summary of the Latest Test Results from Aachen using a TWO CHAMBER Septic Tank as a Settlement Tank

Parameter Results inc. shock and overloading tests Average
BOD5 100% less than 7 mg/L 3.5mg/L
Suspended Solids 100% less than 11 mg/L 2.9mg/L
Ammonia (NH3) 100% less than 9 mg/L 2.7mg/L

The BIOROCK stayed within the UK 20:30:20 standard 100% all of the time. Before you order a rival sewage treatment system, ask the manufacturer for their EN 12566-3 2005 actual test report and compare it with the BIOROCK.
The BIOROCK sewage treatment unit also normally achieves between 1000 to 10,000 times reduction in Thermotolerant Coliform bacteria.

EN 12566-3 2005

Summary of the Test Results from Aachen using SINGLE CHAMBER Settlement Tank

Parameter Results inc. shock and overloading tests Average
BOD5 100% less than 20 mg/L 7.9mg/L
Suspended Solids 100% less than 15 mg/L 7.7mg/L
Ammonia (NH3) 100% less than 20 mg/L 8.8mg/L

BIOROCK sewage treatment units are cleared for sale in the UK as they have the EN12566-3 2005. This more than satisfies the Environment Agency and Building Control requirements.

Last 42 blogs

Show more blogs